What ducting can be used for Edel 200/270L?

Article reference KA-01787

Must comply to air connection and ducting design section on installation instructions.


It is essential to maintain a minimum air flow rate through the ducting for correct operation of the appliance. The nominal mass flow rate must be maintained above 320m3/hr. For the fan to operate in Fan speed 1, the maximum system pressure drop across the ducting connections must not exceed 100Pa and for Fan speed 2 the maximum pressure drop must not exceed 220Pa


The ducting used to connect the air intake and exhaust must be sufficiently insulated to prevent condensation forming. Condensation may result in damage to the appliance and/or building fabric. Dimplex does not take any responsibility for issues caused by poor ducting design or installation.


We don't supply the ducting but can be purchased from Verplas.



Ducting must be installed in accordance with manufactures instructions.



Applicable Models

Edel - EDL200UK-630RF, EDL270UK-630RF, EDL200UK-630, EDL270UK-630